How is Frequency Response/Frequency Bias determined for each Balancing Authority (BA)?
BAL-003-01.b (the Old Rule) gives each BA the freedom to decide what their Frequency Bias Setting should be. BAL-003-1 (the New Rule) mandates how each BA should calculate Frequency Response and in turn decide what the Frequency Bias Setting should be.
NERC's filing explains the how to go from Frequency Response to Frequency Bias Setting very well. Picture a balanced grid suddenly lose one generator,
- The grid is now unbalanced, there's a tendency to extract the kinetic energy stored in the rotating turbines to make up for the loss of generation. The turbines slow down; the frequency of the grid decreases.
- The Governor Control of the turbine senses this decrease in frequency. It opens the valves to let in more fuel, or mechanical input power, to generate more energy. The collective action of all the Governor Controls is the Interconnection's Frequency Response Characteristics. In other words, when a loss of generation happens, to what degree does it affect the frequency and how long does it take the Interconnection to stabilize, or capture the frequency drop. (see following illustration from NERC filing, Exhibit D, p.41)
- What' more interesting is what happens next. After the Governor Control kicks in to capture the frequency drop, the Secondary Response, Automatic Generation Control (AGC) would then try to restore the frequency back to its desired setting. AGC is based on Area Control Error (ACE).
$ACE = [NI_{A} - NI_{S}] - [10B(f_{A}-f_{S})]$
The first bracket is the difference between the actual and scheduled power flows on the tie lines between each BA. If the lost generator is not in the BA (non-contingent BA), from the steps described above, the generators would start to output more energy to counteract the frequency drop, and the actual power flow on the tie lines would be higher than that scheduled. If ACE is only composed of the tie-line exchanges, the first bracket is positive, and the ACE-directed AGC would start to counteract the generators generating more energy.
Hence the second bracket. If B (Frequency Bias Setting) is commensurate with the BA's share of Frequency Response Characteristics, the first and the second brackets would cancel each other out so that the AGC doesn't counteract the generators' Governor Control. Based on the frequency drop profile, I would think that second bracket has to be slightly larger than the first so that the generators not only capture the frequency drop, but also restore the frequency to its original setting. Need to dig in more on this.
The first bracket is the difference between the actual and scheduled power flows on the tie lines between each BA. If the lost generator is not in the BA (non-contingent BA), from the steps described above, the generators would start to output more energy to counteract the frequency drop, and the actual power flow on the tie lines would be higher than that scheduled. If ACE is only composed of the tie-line exchanges, the first bracket is positive, and the ACE-directed AGC would start to counteract the generators generating more energy.
Hence the second bracket. If B (Frequency Bias Setting) is commensurate with the BA's share of Frequency Response Characteristics, the first and the second brackets would cancel each other out so that the AGC doesn't counteract the generators' Governor Control. Based on the frequency drop profile, I would think that second bracket has to be slightly larger than the first so that the generators not only capture the frequency drop, but also restore the frequency to its original setting. Need to dig in more on this.
In summary, Frequency Response is a primary control parameter that the generators react on their own depending on the Interconnection's frequency. Frequency Bias Setting is closely related to Frequency Response, but is a parameter in secondary control. Keep in mind that the difference between primary and secondary control is the time to reaction based on existing (out-dated) capabilities of the generating fleet. New renewable generation and fast-reacting devices may change this scheme completely.
Back to where we started, the loss of generation events that are large enough to observe the Frequency Response Characteristics do not happen very often (good news!). The New Rule defines the qualifications of events to be used to calculate the Frequency Response Characteristics and proposes using medium, instead of mean, of the calculated Frequency Response of each event to be the annual Frequency Response.
So exactly how does the New Rule affect each BA? I think each BA now has to meet a higher standard of Frequency Response. Where would they get this Frequency Response? Exhibit F of the NERC filing documented a survey of how the Governor Control is implemented for different types of generation resources and ERCOT's experiment decreasing the deadband and eliminating step change of Frequency Response. The BAs would have to ask each generator to come up with an improved Governor Control or tap into other types of frequency-responsive resources.
